What is an NTC thermistor?
An NTC thermistor is a temperature-sensitive resistor with a negative temperature coefficient. Its resistance decreases as it gets warmer. A compatible controller reads that resistance and uses the specified resistance–temperature curve to report temperature.
How an NTC thermistor works
A typical controller measures the voltage in a divider that contains the thermistor and a known resistor. The voltage changes as the sensor resistance changes. The direction of that voltage change depends on the circuit and measuring point. Probe position, thermal contact and heat from the measuring current affect how closely the element follows the process temperature.
Compare NTC and PTC thermistors
The coefficient describes how resistance changes with temperature in the specified operating region. Check the device curve and the function it performs in the circuit.
| Type | Resistance as temperature rises | Typical application |
|---|---|---|
| NTC thermistor | Decreases. | Temperature measurement or feedback to a controller that supports the curve. |
| PTC thermistor | Increases in its specified operating region. | Some PTC designs provide a sharp resistance change for overtemperature detection. |
Match R25 and the resistance–temperature curve
R25 is the nominal resistance at 25 °C. The beta value describes the curve over a specified pair of temperatures. In the simple beta approximation, R(T) = R25 × exp[B × (1/T − 1/298.15)], where T is in kelvin. The example shows how two sensors can share the same R25 and differ once they warm up. Use the specified resistance table and tolerance for selection and acceptance.
| Illustrative beta-model inputs | Resistance at 25 °C | Approximate resistance at 50 °C |
|---|---|---|
| B25/85 = 3,435 K | 10.0 kΩ | 4.10 kΩ |
| B25/85 = 3,950 K | 10.0 kΩ | 3.59 kΩ |
How to test an NTC thermistor probe with a multimeter
Follow the equipment isolation procedure before disconnecting the probe. Use a reference thermometer and let the sensing tip reach a stable temperature at each test point. Choose a test setup compatible with the probe and cable seal.
| Step | What to check |
|---|---|
| 1. Measure the disconnected probe | Measure resistance across the sensor terminals. Record the reference temperature and reading, then compare with the specified curve and tolerance. |
| 2. Repeat at another known temperature | Use a point within the probe’s rated range. An NTC reading should fall as the tip warms. Check the resistance at both points against the specified resistance table. |
| 3. Check the measurement chain | If the probe agrees with its table, verify the controller’s configured curve and wiring. If the reading is open or unstable, check the terminals and cable before evaluating the sensor. |
What to send for a replacement probe
Provide the original part reference, controller model and resistance table or R25 and beta value with its temperature pair. Include the tolerance, operating range, mount, insertion length, seal, cable and pinout. Record the temperatures used for any resistance checks.