What is the difference between Pt100 and Pt1000?
A Pt100 has a nominal resistance of 100 Ω at 0 °C. A Pt1000 has 1,000 Ω at 0 °C. For the same platinum curve, the Pt1000 changes resistance by ten times as much per degree. The instrument must support the chosen nominal resistance and wiring.
Compare resistance and wiring
The nominal values below use the IEC 60751 platinum curve. Sensitivity is averaged from 0 °C to 100 °C and varies with temperature.
| Measurement | Pt100 | Pt1000 |
|---|---|---|
| Nominal resistance at 0 °C | 100 Ω | 1,000 Ω |
| Nominal resistance at 100 °C | 138.5 Ω | 1,385 Ω |
| Average sensitivity from 0 to 100 °C | 0.385 Ω/°C | 3.85 Ω/°C |
| Instrument input | Pt100 curve and wire count | Pt1000 curve and wire count |
Estimate lead-wire error
In a two-wire circuit, 2 Ω of total lead resistance corresponds to about 5.2 °C error for Pt100 or 0.52 °C for Pt1000 using the average sensitivity in the table. This example assumes constant lead resistance. Three-wire and four-wire inputs with compatible probes can reduce lead error when a longer cable or tighter tolerance is required.
Check excitation and self-heating
An RTD dissipates electrical power from the measuring current. At the same current a Pt1000 dissipates more power than a Pt100 at the same temperature. Use the excitation specified for the input and element. Probe size, mounting and the process medium affect how much sensor temperature rises.
Check whether the sensors can be interchanged
Choose the type supported by the controller or transmitter. A replacement also needs the correct wire count, tolerance class, insertion dimensions and sheath. The complete error budget includes the element, lead wiring, electronics, mounting and any thermal gradients.