Selection guide

Pt100 RTD Wiring Diagram for 2, 3 and 4 Wires

Use 2-, 3- and 4-wire Pt100 diagrams to identify leads, check RTD resistance and match the sensor to your transmitter, PLC input or controller.

How do I wire a Pt100 RTD?

Identify the two ends of the platinum element and select the matching RTD input mode. A two-wire sensor has one lead per end, a three-wire sensor has two leads at one end, and a four-wire sensor has two leads at each end. Match these pairs to the terminal drawing for your instrument.

Identify the element ends

A and B in these diagrams are the ends of one Pt100 sensing element. A1 and A2 share one end, and B1 and B2 share the other. Use the probe drawing to identify the pairs, especially for dual-element assemblies.

Two-wire Pt100 wiring

Two leads complete the measuring circuit. The instrument sees the element resistance plus the resistance of both leads. Check the expected lead resistance at the installed length when evaluating measurement error.

One lead to each end of the element

Three-wire Pt100 wiring

Two leads connect to the same end of the element. A compatible three-wire input estimates lead resistance and compensates for it when the relevant lead resistances match. Use matched wire lengths and gauges through cable extensions and terminations.

A1 and A2 connect to the same end

Four-wire Pt100 wiring

Each end has a current lead and a voltage-sense lead. With a compatible four-wire input, the voltage measurement excludes most of the drop along the current leads. Connect each pair to the instrument terminals marked for that end of the element.

Two leads to each end of the element

How do I check an RTD sensor?

Isolate power to the instrument input and disconnect the sensor. Let the probe stabilize at a known temperature. Use a resistance meter across leads from opposite ends and compare the reading with the curve for that RTD. At 25 °C, a nominal IEC 60751 Pt100 measures about 109.7 Ω and a Pt1000 about 1,097 Ω, before lead resistance and tolerance. A spot check can identify common wiring faults. Verify calibration separately when the process requires it.

How do I check an RTD sensor?
ObservationWhat to check
Low resistance between leads on the same endThat reading can be normal for a shared element end. Identify the opposite lead pair and measure across the element.
Open or overrange across the elementConfirm the selected meter range and check for a disconnected terminal, broken lead or open element.
Unusually low resistance across the elementDouble-check the lead pairing before checking for a short across the leads or inside the probe.
Normal probe reading with an incorrect controller readingVerify the selected Pt100 or Pt1000 curve, wire count and terminal assignments at the input.

Check the transmitter or PLC input

Set the input to the correct platinum curve and wire count. The manufacturer’s diagram specifies terminal numbers, any jumpers for supported two-wire connections, and shield termination. For a custom probe, send the instrument model, lead length, wiring mode, operating temperature and the required system accuracy.