Thermocouple Wire Color Codes and Polarity

Compare US ANSI/ASTM and IEC thermocouple wire colors for Types K, J, T, E and N. Specify compatible Type R and Type B cables and polarity.

What color is the negative thermocouple wire?

For Types K, J, T, E and N, the negative conductor is red under US ANSI/ASTM conventions and white under IEC 60584-3. Check the marked thermocouple type, the applicable standard and the instrument terminals before wiring.

US and IEC conductor colors

The chart compares insulated conductor colors. Jacket colors vary with cable grade and standard. Older assemblies may follow a different national convention.

US and IEC conductor colors
TypeUS +US −IEC +IEC −
KYellowRedGreenWhite
JWhiteRedBlackWhite
TBlueRedBrownWhite
EPurpleRedVioletWhite
NOrangeRedPinkWhite

Identify the pair before making a connection

Read the printing on the cable or probe label. Check the type and polarity markings on the connector and the input terminals. Set the transmitter to the same alloy type. If the markings are unclear, identify the assembly from its part documentation or verify its response with a known reference before putting it into service.

Extension wire and compensating cable

Extension-grade cable uses conductors of the same nominal composition as the corresponding thermocouple pair. Compensating cable uses different alloys chosen to reproduce the needed thermoelectric behavior over a specified temperature interval. Select an approved cable designation for the thermocouple and verify the range for the junctions and the insulation.

Type R and Type B cable and polarity

Match the extension or compensating cable designation to the instrument and probe documentation. Use the conductor colors specified for that cable grade and standard, and verify polarity at the connector and input. Include the expected temperature at each transition in the wiring specification.

Type R and Type B cable and polarity
TypeWhat to check
RType R input, cable grade and color standard, connector polarity and allowed transition temperature.
BType B input and measurement interval, compatible cable designation, head terminal markings and transition temperature.

Specify a replacement cable or connector

Send the type, color standard, connector format, lead length and maximum cable temperature. For a junction box or extension run, include the expected temperature at both ends and any shield or abrasion requirements.

Have a specification to review?

Share your equipment, operating conditions and dimensions in a custom RFQ.