Selection guide

How to Test an Industrial Thermocouple

Test industrial thermocouple continuity, sheath isolation and voltage with a multimeter. Use the Type K millivolt chart with a 0 °C reference.

How do I test a thermocouple with a multimeter?

With the probe isolated from the instrument and process equipment, check continuity between its two leads. Compare lead-to-sheath continuity with the specified junction type. Then use a DC millivolt meter and a controlled temperature source to check signal polarity and response. Use a thermocouple meter or calibrator for a compensated temperature reading.

Identify the probe and isolate the measurement circuit

Record the thermocouple type, junction, terminal polarity and the fault shown by the instrument. Follow the equipment isolation procedure before disconnecting the leads. Use a controlled bench setup to test a probe that has been safely removed. This procedure covers industrial thermocouple measurement probes.

Check conductor continuity and sheath isolation

Check resistance across the disconnected thermocouple leads. The expected reading depends on alloy, wire size and length. Use the probe wiring diagram when an assembly has more than one sensing circuit.

Check conductor continuity and sheath isolation
Meter observationWhat to check
Open or overrange across the two leadsVerify meter contact and any intermediate connections. Compare readings at successive accessible terminations to trace an open probe or cable.
Intermittent reading during a stationary bench checkCheck loose terminals, damaged flex points and the lead transition for intermittent contact.
Continuity from a lead to the sheathA grounded junction has an electrical connection to the sheath. An ungrounded junction calls for isolation under its specified test conditions.
Stable resistance across the lead pairThe circuit has continuity. Check the millivolt response and, where required, calibration separately.

Check millivolt polarity and response

Connect the probe to the DC millivolt input with the expected polarity. Apply a known temperature change to the sensing tip while keeping the reference connections together at a stable, known temperature. Compare the reading with the difference between the reference table values for the tip and the reference connections.

Check millivolt polarity and response
Type K exampleExpected result
100 °C tip and 0 °C referenceApproximately +4.096 mV at the specified polarity.
100 °C tip and 25 °C referenceApproximately +3.096 mV, the difference between about 4.096 mV and 1.000 mV.
Tip and reference at the same temperatureApproximately 0 mV. The two reference voltages cancel when both junctions are at the same temperature.

Troubleshoot open, drifting or intermittent readings

Record the symptom and the process conditions when it occurs. Follow the equipment isolation procedure before checking wiring or disconnecting the probe.

Troubleshoot open, drifting or intermittent readings
Observed symptomWhat to check
Open-input alarm or loss of signalConfirm the configured input and trace continuity through the probe and extension leads. Check accessible terminals to locate an open section.
Reading falls when the tip is warmedWith the reference connections at a stable temperature, compare lead polarity at the probe, connector and instrument.
Intermittent jumps during operationLook for loose terminals and damage at flex points. Note vibration, switching loads and cable routing when the fault occurs.
Drift or a persistent offsetConfirm the input type, extension cable, cold-junction compensation and installed tip position. Compare with a suitable reference at defined test points to separate probe drift from a circuit or installation issue.

Type K Thermocouple Millivolt Chart

These selected NIST ITS-90 values use a 0 °C (32 °F) reference junction. For a DC millivolt reading at another known terminal temperature, subtract the chart value for the reference junction from the chart value for the sensing tip. Use the full NIST reference for intermediate values.

Type K Thermocouple Millivolt Chart
Sensing tip (°C)Sensing tip (°F)Voltage relative to 0 °C
−200 °C−328 °F−5.891 mV
−100 °C−148 °F−3.554 mV
−50 °C−58 °F−1.889 mV
0 °C32 °F0.000 mV
25 °C77 °F1.000 mV
50 °C122 °F2.023 mV
100 °C212 °F4.096 mV
150 °C302 °F6.138 mV
200 °C392 °F8.138 mV
300 °C572 °F12.209 mV
400 °C752 °F16.397 mV
500 °C932 °F20.644 mV
600 °C1112 °F24.905 mV
800 °C1472 °F33.275 mV
1000 °C1832 °F41.276 mV
1200 °C2192 °F48.838 mV

Check the controller if the probe responds

Confirm the instrument is set to the correct thermocouple type. Compare its terminal polarity and extension cable designation with the probe. Check that the instrument reference compensation uses the temperature at the actual reference connections. For calibration, compare against a traceable reference at the required test points.

What to send when replacing an industrial probe

Share the sensor drawing or original marking, type, junction, mount and installed insertion length. Include process temperature, atmosphere, lead details, instrument model and the symptom you observed.